打开提示启动本地服务器后,出现:cannot open wincc project,project manager for configured server is not running
最佳答案
1.打开Start -> Programs -> Microsoft SQL Server 200x->Configuration Tools ->SQL Server Configuration Server看看服务器有没有启动。
2.参考英文论坛的处理方法试试:
I resolved the isuse as follows:
1) Moved the Projekt to C:Documents and SettingsAll UsersDocumentsSiemensWinCCProjects————移动项目到C:Documents and SettingsAll UsersDocumentsSiemensWinCCProjects目录下。
2) Recursively removed the Read Only attrubutes (at some point the project was on a CD and this attribute wanders along untill explicitely removed.)
3) Recursively removed the "Compressed" property
参考资料:http://www.automation.siemens/WW/forum/guests/PostShow.aspx?PostID=202902&language=en