Motor Starter Protectors/Circuit BreakersSIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80 A■Overview
The following illustration shows our 3RV2 motor starter
Accessories, see page 7/31 tor/circuit breaker with the accessories which can be
mounted for the sizes S00 to S2, see also "Introduction" ➞
"Overview", page 7/ble accessories71Transverse auxiliary switch2Lateral auxiliary switch with 2 contacts3Lateral auxiliary switch with 4 contacts4Shunt release (can not be used with 3RV21
8motor starter protectors)5Undervoltage release without/with
3leading contacts (can not be used with
3RV21 motor starter protectors)6Signaling switch (can not be used with
23RV27 and 3RV28 circuit breakers)7Isolator module (can not be used with
3RV27 and 3RV28 circuit breakers)68Terminal block type E
or phase barriers41a67020_50BSNMountable accessories for SIRIUS 3RV2 motor starter protectors/circuit breakersThe new SIRIUS 3RV2 motor starter protectors/circuit breakers
are compact, current limiting motor starter protectors/circuit
breakers which are optimized for load feeders. The motor starter
protectors/circuit breakers are used for switching and protecting
three-phase motors of up to 37 kW at 400 V AC and for other
loads with rated currents of up to 80 3RV1 motor starter protectors/circuit breakers in size S3 up
to 100 A, see page 7/63 new 3RV2 motor starter protectors/circuit breakers are
usually approved according to IEC and UL/CSA. According to
UL 508/UL 60947-4-1, the 3RV2 motor starter protectors
in sizes S00 to S2 are approved as:•"Manual Motor Controllers"•"Manual Motor Controllers" for "Group Installations"•"Manual Motor Controllers Suitable for Tab Conductor
Protection in Group Installations"•"Self-Protected Combination Motor Controllers (Type E)"Please note that for this approval the 3RV20 motor starter
SIRIUS motor starter protector with spring-type terminals, size S0 (left)protectors must be equipped with additional infeed terminals
and SIRIUS motor starter protector with screw terminals, size S00 (right)
or phase barriers. More information, see "Accessories" on
page 7/38.
Corresponding short-circuit values, see pages 7/10 to 7/ 3RV27 and 3RV28 circuit breakers are approved as circuit
breakers according to UL 489; they are a special version of the
3RV2 motor starter protectors.7/77
Motor Starter Protectors/Circuit BreakersSIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80 AType of constructionThe 3RV2 motor starter protectors are available in three sizes:•Size S00 – width 45 mm,
max. rated current 16 A,
at 400 V AC suitable for three-phase motors up to 7.5 kW•Size S0 – width 45 mm,
max. rated current 40 A,
at 400 V AC suitable for three-phase motors up to 18.5 kW•Size S2 – width 55 mm,
max. rated current 80 A,
at 400 V AC suitable for three-phase motors up to 37 kWSize S3 of the 3RV1 motor starter protectors up to 100 A,
see page 7/63 t breakers acc. to UL 489The 3RV27 and 3RV28 circuit breakers are available in two sizes:•Size S00 – width 45 mm,
max. rated current 15 A, for 480 Y/277 V AC•For size S0 – width 45 mm,
max. rated current 22 A, at 480 Y/277 V ACFor size S3 of the 3RV1742 circuit breakers up to 70 A,
see page7/tion methodsThe 3RV2 motor starter protectors/circuit breakers can be
supplied with screw terminals, spring-type terminals and ring
cable lug terminalsSpring-type terminalsRing terminal lug connectionsThe terminals are indicated in the corresponding
tables by the symbols shown on orange
backgrounds."Increased safety" type of protection EEx e according to
ATEX directive 94/9/EC
3RV20 motor starter protectors are suitable for overload
protection of explosion-proof motors with "increased safety"
typeof protection EEx type test certificate for Category (2) G/D has been submitted.
More details on hensive technical information, see
manuals/operating instructions,
/WW/view/en/20357458/133300.7Article No. schemeDigit of the Article starter protectors/circuit breakers
SIRIUS 2nd generationType of motor starter protector/circuit breakerSizeBreaking capacitySetting range for overload releaseTrip class (CLASS)Connection methodsWith or without auxiliary switchSpecial versionsExample3 R V2011–1AA101st - 3rd@@@3 R V2@@@@@@@@@@@@4th5th6th7th@@@@–8th9th10th11th12th@@@@@–13th14th15th16th@@@@Note:The Article No. scheme is presented here merely for information
purposes and for better understanding of the logic behind the
article numbers.
For your orders, please use the article numbers quoted in the
catalog in the Selection and ordering data.
Motor Starter Protectors/Circuit BreakersSIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 80 A■BenefitsAdvantages through energy efficiencyWe offer you a unique portfolio for industrial energy manage-ment, using an energy management system that helps to
optimally define your energy needs. We split up our industrial
energy management into three phases – identify, evaluate and
realize – and we support you with the appropriate hardware and
software solutions in every process innovative products of the SIRIUS industrial controls portfo-lio can also make a substantial contribution to a plant's energy
efficiency (see /sirius/energysaving).3RV2 motor starter protectors/circuit breaker contribute to
energy efficiency throughout the plant as follows:4•Minimization of energy losses through optimization of the
4200bimetal trip units_10CI•Reduction of inherent power loss•Less heating of the control cabinetOverview of the energy management process•Smaller control cabinet air conditioners can be used■ApplicationOperating conditionsPossible uses3RV2 motor starter protectors/circuit breakers are suitable for The 3RV2 motor starter protectors can be used:use in any climate. They are intended for use in enclosed rooms
in which no severe operating conditions (such as dust, caustic
•For short-circuit protection
vapors, hazardous gases) prevail. When installed in dusty and
•For motor protection (also with overload relay function)
damp areas, suitable enclosures must be provided.•For system protection
3RV2 motor starter protectors/circuit breakers can optionally be
•For short-circuit protection for starter combinations
fed from the top or from below.•For transformer protection
The permissible ambient temperatures, the maximum switching
•As main and EMERGENCY-STOP switches
capacities, the tripping currents and other boundary conditions
can be found in the technical specifications and tripping charac-•For operation in IT systems (IT networks)
teristics, see the manual
•For switching of DC currents
"SIRIUS Innovations – SIRIUS 3RV2 Motor Starter Protectors",
•In areas subject to explosion hazard (ATEX)/WW/view/en/60279172.•Approved as circuit breakers according to UL 489
3RV2 motor starter protectors/circuit breakers are suitable for
(3RV27 and 3RV28)operation in IT systems (IT networks). In this case, the different
short-circuit breaking capacity in the IT system must be taken
For more information, seeinto account, see page 7/11.•System manual "SIRIUS Innovations – System Overview",
/WW/view/en/60311318Since operational currents, starting currents and current peaks
are different even for motors with identical power ratings due to
•Manual "SIRIUS Innovations – SIRIUS 3RV2 Motor Starter
the inrush current, the motor ratings in the selection tables are
Protectors",
only guide values. The specific rated and startup data of the
/WW/view/en/60279172
motor to be protected is always paramount to the choice of the
most suitable motor starter protector/circuit breaker. This also
applies to motor starter protectors for transformer :For the use of 3RV2 motor starter protectors in conjunction with
highly energy-efficient IE3 motors, please observe the informa-tion on dimensioning and configuring, see
"ConfigurationManual for SIRIUS Controls with IE3 Motors",
/WW/view/en/ information, see 1/3.7
Motor Starter Protectors/Circuit BreakersSIRIUS 3RV2 Motor Starter Protectors up to 80 A■Selection and ordering data
CLASS 10, without auxiliary switches1) PU (UNIT, SET, M)= 1PS*= 1 unitPG= 41E3RV2011-0AA103RV2011-0EA203RV2021-4AA103RV2021-4AA20Rated Suitable for Setting range for Instantaneous Short-circuit DTScrew terminalsDTSpring-type
currentthree-phase thermal overload overcurrent breaking capacity terminalsmotors2) with Preleasereleaseat400 V ACInIcuArticle rticle kWAAkAper PUper PUSize S000.160.040.11 ... 0.162.1100}3RV2011-0AA10}3RV2011-0AA200.20.060.14 ... 0.22.6100}3RV2011-0BA10}3RV2011-0BA200.250.060.18 ... 0.253.3100}3RV2011-0CA10}3RV2011-0CA200.320.090.22 ... 0.324.2100}3RV2011-0DA10}3RV2011-0DA200.40.090.28 ... 0.45.2100}3RV2011-0EA10}3RV2011-0EA200.50.120.35 ... 0.56.5100}3RV2011-0FA10}3RV2011-0FA200.630.180.45 ... 0.638.2100}3RV2011-0GA10}3RV2011-0GA200.80.180.55 ... 0.810100}3RV2011-0HA10}3RV2011-0HA2010.250.7 ... 113100}3RV2011-0JA10}3RV2011-0JA201.250.370.9 ... 1.2516100}3RV2011-0KA10}3RV2011-0KA201.60.551.1 ... 1.621100}3RV2011-1AA10}3RV2011-1AA2020.751.4 ... 226100}3RV2011-1BA10}3RV2011-1BA202.50.751.8 ... 2.533100}3RV2011-1CA10}3RV2011-1CA203.21.12.2 ... 3.242100}3RV2011-1DA10}3RV2011-1DA2041.52.8 ... 452100}3RV2011-1EA10}3RV2011-1EA2051.53.5 ... 565100}3RV2011-1FA10}3RV2011-1FA206.32.24.5 ... 6.382100}3RV2011-1GA10}3RV2011-1GA20835.5 ... 8104100}3RV2011-1HA10}3RV2011-1HA201047 ... 10130100}3RV2011-1JA10}3RV2011-1JA2012.55.59 ... 12.5163100}3RV2011-1KA10}3RV2011-1KA20167.5103) ... 1620855}3RV2011-4AA10}3RV2011-4AA20Size S00.630.180.45 ... 0.638.2100B3RV2021-0GA10B3RV2021-0GA200.80.180.55 ... 0.810100B3RV2021-0HA10B3RV2021-0HA2010.250.7 ... 113100B3RV2021-0JA10B3RV2021-0JA201.250.370.9 ... 1.2516100B3RV2021-0KA10B3RV2021-0KA201.60.551.1 ... 1.621100B3RV2021-1AA10B3RV2021-1AA2020.751.4 ... 226100B3RV2021-1BA10B3RV2021-1BA202.50.751.8 ... 2.533100B3RV2021-1CA10B3RV2021-1CA203.21.12.2 ... 3.242100B3RV2021-1DA10B3RV2021-1DA2041.52.8 ... 452100B3RV2021-1EA10B3RV2021-1EA2051.53.5 ... 565100B3RV2021-1FA10B3RV2021-1FA206.32.24.5 ... 6.382100B3RV2021-1GA10B3RV2021-1GA20835.5 ... 8104100B3RV2021-1HA10B3RV2021-1HA201047 ... 10130100B3RV2021-1JA10B3RV2021-1JA2012.55.59 ... 12.5163100B3RV2021-1KA10B3RV2021-1KA20167.5103)20855}3RV2021-4AA10}3RV2021-4AA20207.53) ... 1613 ... 2026055}3RV2021-4BA10}3RV2021-4BA202211163)28655}3RV2021-4CA10}3RV2021-4CA2025113) ... 2218 ... 2532555}3RV2021-4DA10}3RV2021-4DA20281523 ... 2836455}3RV2021-4NA10}3RV2021-4NA20324)1527 ... 3240055}3RV2021-4EA10}3RV2021-4EA20365)18.530 ... 3643220}3RV2021-4PA10--405)18.534 ... 4048020}3RV2021-4FA10--1)The 3RV20.1-..A.0 motor starter protectors up to 32 A are also available
4)Suitable for use with IE3 motors up to a starting current of 256 A. For higher
with ring terminal lug connection. The Article No. must be changed in the starting currents we recommend using 3RV2 motor starter protectors
11th digit to "4": e.g. 2.2)Guide value for 4-pole standard motors at 50 Hz
400 V AC. The actual
5)The devices must not be mounted side-by-side and they must not be
starting and rated data of the motor to be protected must be considered assembled with link modules with contactors. A lateral clearance of 9 mm
when selecting the required. For use with IE3 motors we recommend using 3RV2 motor
3)The setting range of the thermal overload releases has been r protectors size ary switches and other accessories can be ordered
separately (see "Accessories" page 7/32 onwards).*You can order this quantity or a multiple thereof.7/217